Routine inspection and maintenance checks for wastewater lift stations, organized by frequency, with the readings to record each visit.

Updated November 21, 2026 · Reviewed against 3 official and primary sources · Editorial standards

A lift station inspection checklist records, on each visit, the wet well level and condition, pump run hours, starts and amperage, level control and alarm function, telemetry, standby generator and transfer switch status, valves, odor control and security, plus any work performed. Daily or weekly checks catch failures early; monthly and annual tasks keep equipment within manufacturer guidance.

How to use this checklist

Adapt frequencies to each station's size, criticality and whether it has remote monitoring, and to your NPDES permit and state requirements. Record readings, not just ticks: trends in run hours, starts and amperage show a pump wearing before it fails. Lift station failures are a common cause of sanitary sewer overflows; see the sanitary sewer overflow guide for reporting. Manufacturer operation and maintenance manuals govern equipment-specific tasks.

Visit header

Station name / ID
Date and time in / out
Operator(s)
Weather / conditions
Reason for visit (routine / alarm / complaint / other)

Routine visit (daily or weekly)

Site and security

Wet well

Pumps

ReadingPump 1Pump 2Pump 3
Run hours (meter)
Starts (counter)
Amperage (each phase)
Discharge pressure
Unusual noise / vibration / heat
Alternation working

Controls, alarms and telemetry

Standby power

Monthly

Quarterly to annual

Work performed and follow-up

Issue foundAction takenWork order numberFollow-up needed

Operator signature and date.

Keeping the record useful

Inspection logs are most valuable when readings are tracked over time and tied to work orders, so a rising amperage or starts count prompts maintenance before an overflow. They also document the station's condition before a disaster, which matters when damage is claimed under FEMA Public Assistance. In Elarchon, Lift Station Monitoring, Work Orders and the GIS Asset Registry share one record. See water and wastewater.

Questions

What should a lift station inspection include?

Wet well level and condition, pump operation (run hours, starts, amperage, noise and vibration), level controls and floats, alarms and telemetry, standby power and transfer switch, valves and piping, odor control, security, and a log of readings and work performed.

How often should lift stations be inspected?

Frequency depends on the station's size, criticality, telemetry and your permit and state requirements. Stations without remote monitoring are typically visited more often. Set frequencies in your operations and maintenance program and follow manufacturer guidance.

Why do lift station records matter for compliance?

Lift station failures can cause sanitary sewer overflows. Overflow reporting and proper operation and maintenance obligations are set by your NPDES permit and state rules; inspection records show the station was operated and maintained as required.

Should generator tests be part of the lift station checklist?

Yes. Standby power keeps pumps running during outages. Record generator exercise runs, transfer switch tests, fuel level and any faults.

How do lift station inspections connect to disaster reimbursement?

After a declared disaster, records of pre-disaster maintenance and condition help show that damage to the station was caused by the event. FEMA Public Assistance reviews facility condition for permanent work.

Sources

  1. Sanitary sewer overflows (SSOs) U.S. Environmental Protection Agency
  2. 40 CFR Part 122 (NPDES permit program) eCFR
  3. Water utility emergency response U.S. Environmental Protection Agency

Request a briefing

See Elarchon configured for your jurisdiction.

Briefings are prepared around your departments, incident types and reporting obligations.

Request a briefing