Hydrant flow test: procedure, NFPA 291 and color coding

A hydrant flow test measures how much water a hydrant and the main behind it can deliver, so firefighters know the available fire flow and utilities know the strength of the system. This guide covers the method, the 20 psi rating, NFPA 291 color codes and the record each test should produce.

Updated November 21, 2026 · Reviewed against 5 official and primary sources · Editorial standards

A hydrant flow test measures static pressure at a test hydrant, then flows nearby hydrants while recording the pitot pressure at each flowing outlet and the residual pressure at the test hydrant. From the static pressure, residual pressure, pitot pressure, outlet size and number of outlets, the available flow is calculated at 20 psi residual, which is the basis for NFPA 291's hydrant color classes.

Why flow testing matters

Firefighters need to know how much water a hydrant can deliver before they rely on it. Water utilities need to know where mains are undersized or valves are closed. Flow tests also feed the water supply portion of the ISO PPC rating, which ISO weights at 40 of its points in the Fire Suppression Rating Schedule. Because fire departments and water utilities both depend on the same hydrants, the test is usually a joint responsibility.

The test method

The Tennessee Municipal Technical Advisory Service describes the method recognized by ISO and NFPA, based on AWWA Manual M17:

  1. Choose the test hydrant, the one where pressure will be measured, and one or more flow hydrants on the same main, typically downstream and upstream.
  2. Install a cap gauge on the test hydrant and record the static pressure with no water flowing.
  3. Open the flow hydrants, using as many outlets and sizes as needed to produce a significant drop in pressure.
  4. Record the pitot pressure at each flowing outlet with a pitot gauge, and the outlet diameter.
  5. Record the residual pressure at the test hydrant while the flow hydrants are open.
  6. Close the hydrants slowly to avoid water hammer, and flush or notify customers as your utility requires.
  7. Calculate the flow in gallons per minute from the pitot readings, outlet size and number of outlets, then project the flow available at 20 psi residual using the static and residual pressures.

MTAS notes that multi-hydrant tests are more accurate than single-hydrant tests, where one hydrant is used for static, residual and pitot readings. The 2022 edition of NFPA 291 separated the procedure for evaluating a water main's supply from the procedure for evaluating an individual hydrant.

The five numbers every test produces

ReadingWhere
Static pressureTest hydrant, no flow
Residual pressureTest hydrant, while flow hydrants are open
Pitot (flow) pressureEach flowing outlet
Outlet sizeEach flowing outlet
Number of outlets flowingFlow hydrants

NFPA 291 color codes

NFPA 291 recommends painting the bonnet and nozzle caps to show capacity at 20 psi residual. MTAS summarizes the classes from NFPA 291 Table 5.1:

ClassBonnet and cap colorAvailable flow at 20 psi
AALight blue1,500 gpm or more
AGreen1,000 to 1,499 gpm
BOrange500 to 999 gpm
CRedBelow 500 gpm

The recommended barrel color for public hydrants is chrome yellow unless the jurisdiction has adopted another; private hydrants should be distinguished from public ones, and hydrants on non-potable supplies are commonly violet. MTAS points out that a frequent error is coloring hydrants by the flow observed during the test rather than the flow calculated at 20 psi.

NFPA 291 is a recommended practice. Its color scheme is enforceable only where a jurisdiction adopts it, and many communities use a local variation. Use the scheme your jurisdiction has adopted.

The record each test should leave

A complete record includes the date and time, test and flow hydrant identifiers and locations, main size, the five readings, the calculated flow at 20 psi, the resulting class, who performed the test, and any problems found (stuck valves, leaks, low pressure). The record should be attached to the hydrant itself so it is visible to both the fire department and the utility. See the hydrant flow test form.

How Elarchon helps

Hydrant Management in Elarchon records flow tests, out-of-service status and maintenance history for each hydrant, and the same hydrant appears in the water utility's GIS asset registry and on fire crews' pre-incident maps. See hydrant management.

Questions

What is a hydrant flow test?

A test that measures static pressure at a test hydrant, then flows one or more nearby hydrants while recording pitot pressure at each flowing outlet and the residual pressure at the test hydrant. The results are used to calculate the flow available at a chosen residual pressure, typically 20 psi.

During a hydrant flow test, where is residual pressure measured?

At the test hydrant, which is not flowing. The flow hydrants discharge water, and the residual pressure is read on a cap gauge at the test hydrant while they flow.

Why are hydrants rated at 20 psi?

Twenty psi residual is the pressure commonly used to rate available fire flow, leaving a margin to protect the water system and fire pumps. NFPA 291's color classes are based on available flow at 20 psi residual.

What do hydrant colors mean?

Under NFPA 291's recommended scheme, the bonnet and caps show capacity: light blue Class AA (1,500 gpm or more), green Class A (1,000 to 1,499 gpm), orange Class B (500 to 999 gpm) and red Class C (below 500 gpm), at 20 psi residual. Chrome yellow is the recommended barrel color for public hydrants.

How often should hydrants be flow tested?

There is no single national interval for public hydrants. Frequency is set by the adopted fire code, the water utility's policy and ISO's water supply evaluation. Many systems test on a multi-year cycle and after significant system changes.

Is NFPA 291 mandatory?

No. NFPA 291 is a recommended practice. Its testing method and color scheme are enforceable only where a jurisdiction adopts them.

Sources

  1. NFPA 291: Recommended Practice for Water Flow Testing and Marking of Hydrants National Fire Protection Association
  2. Flow test a fire hydrant University of Tennessee Municipal Technical Advisory Service
  3. Marking all fire hydrants University of Tennessee Municipal Technical Advisory Service