Hydrant flow test form

A field form for two-hydrant flow tests, with the readings to record and the calculations for flow and available fire flow.

Updated November 21, 2026 · Reviewed against 3 official and primary sources · Editorial standards

A hydrant flow test form records the test hydrant's static and residual pressures, each flowing outlet's size, coefficient and pitot pressure, and the calculated flow, then the available flow at 20 psi residual. Flow per outlet is commonly calculated as Q = 29.83 × c × d² × √p, and available flow as Q20 = QF × ((S − 20) / (S − R))^0.54.

How to use this form

Use one form per test. Coordinate with the water utility before flowing hydrants, notify affected customers where required, and manage discharge to avoid flooding or erosion. Procedures, coefficients and hydrant marking follow NFPA 291; the formulas below follow the University of Tennessee MTAS guide Conducting a Fire Flow Test. For planning a testing program, see the hydrant flow testing guide.

Test header

Test ID
Date and time
Tested by / agency
Water utility contact notified
Location / street
Main size and material (if known)
Pressure zone
System conditions (pumps running, tank levels, unusual demand)

Residual (test) hydrant

Hydrant ID
Location
Static pressure, S (psi)
Residual pressure while flowing, R (psi)

Flow hydrant(s)

Hydrant IDOutlet usedOutlet diameter, d (in)Coefficient, cPitot pressure, p (psi)Flow, Q (gpm)
Total test flow, QF

Calculations

Flow from each outlet

Q = 29.83 × c × d² × √p

Add the flows from all outlets flowing at the same time to get QF.

Available flow at 20 psi residual

Q20 = QF × ((S − 20) / (S − R))^0.54

Worked layout

StepValue
S (static)__ psi
R (residual)__ psi
QF (total test flow)__ gpm
(S − 20) ÷ (S − R)__
Raised to the 0.54 power__
Q20 = QF × result__ gpm

Results and follow-up

Why flow test records matter

Flow tests feed pre-incident plans, fire protection system design reviews and the water supply portion of an ISO Public Protection Classification review. They are most useful when stored against the hydrant record that both the fire department and the water utility use. In Elarchon, hydrant management keeps inspections, flow tests and out-of-service status on one hydrant record shared by fire and water.

Questions

What does a hydrant flow test measure?

The water supply available at a location: the static pressure in the main, the residual pressure while water flows, and the flow from one or more outlets, from which the available flow at a chosen residual pressure (commonly 20 psi) is calculated.

How is hydrant flow calculated from a pitot reading?

A common form of the formula is Q = 29.83 × c × d² × √p, where Q is flow in gallons per minute, c is the outlet coefficient, d is the outlet diameter in inches and p is the pitot pressure in psi. Sum the flow of all flowing outlets.

How is available flow at 20 psi residual calculated?

Using the measured flow and pressures: Q20 = QF × ((S − 20) / (S − R))^0.54, where QF is the test flow, S is static pressure and R is residual pressure.

Which standard covers hydrant flow testing?

NFPA 291 is the recommended practice for fire flow testing and marking of hydrants. Check the current edition for coefficients, procedures and marking colors.

How many hydrants are needed for a flow test?

A standard test uses at least two: a residual (test) hydrant where static and residual pressures are read, and one or more flow hydrants. The Tennessee MTAS guidance notes that neither NFPA nor AWWA recommends the single-hydrant method.

Sources

  1. NFPA 291: Recommended Practice for Water Flow Testing and Marking of Hydrants National Fire Protection Association
  2. Conducting a fire flow test University of Tennessee Municipal Technical Advisory Service
  3. Public Protection Classification (PPC) ISO / Verisk